Brand Name: TEREN
Model Number: D5P
Place of Origin: Guangdong, China (Mainland)
D5 Mini Digital Differential Pressure Gauge/Controller/Transmitter
D5/ D5P/ D5G/ D5T with the same design as below, power, range, relay, output are optional.
Applications & Features
Specifications
Medium: non-combustible, non-corrosive air, not sensitive to moisture, dust, condensation and oil
Working Temp. : D5:-10~50°C, D5P/G/T:-20~70°C
Medium Temp.: 0~60°C
Temp. Compensation: 0~50°C
Working pressure: overload 10xFS, burst 15xFS
Display: 4 bits LCD, with engineering unit, with backlight (except D5)
Output: 0-10V / 4-20mA(3 wires)
Output load: ≤500Ω(current), ≥2KΩ(voltage)
Digital Output: RS485/Modbus (9600-n-8-1)
Relay Output: 2×SPST,1A/30VDC, or 1x Buzzer
Accuracy up to: ±1.0% FS, see accuracy table
Long term stability: ±0.5%FS /Year
Thermal effect: <0.05%FS/°C(zero), <0.08%FS/°C(FS)
Battery type(D5):
Power: AA battery X4, recommend LR6 alkaline
Display update time: selectable for 0.5/1/5/10s(default1s)
Automatic sleep time: selectable for normal open(on), or1/5/10min(default 1min)
Battery service life: When display update time=1s and automatic sleep time=on, ≥2 year;
When display time>1s or automatic sleep time≥1min, will be longer.
It also depends on the quality of the batteries.
Power type(D5P/D5G/D5T): 15~28VDC/AC
Long term stability: ±0.5%FS /Year
Thermal effect: <0.05%FS/℃(zero), <0.08%FS/ ℃(FS)
Process Connection: 5mm ID tubing, two pairs(on left or back side)
Keys: 3 touch buttons
Protection: IP65
Weight: 220g(battery type incl. batteries), 180g(power type)
Materials: ABS
Approval: CE
Accessory: A-S0 is standard. It can be used for surface or panel mount. See details in Accessories.
Models
1. D5/ D5P Models
Model |
D5 |
Mini Digital DP Gauge (Battery type) |
|
D5P |
Mini Digital DP Gauge (Power type) |
||
Range |
See table |
Only ranges 3,5,7,8 are available |
2. D5G Models
Model | D5G |
Mini multi-function Digital DP Gauge |
||
Range |
See table |
|
|
|
Relay |
|
1 | 2xSPST |
|
2 | 1xbuzzer |
3. D5T Models
Model | D2PL |
|
Mini multi-function Digital DP |
||
Range |
See table |
|
|
||
Relay | 0 |
N/A |
|||
|
1 | 2xSPST |
|||
2 | 1xBuzzer | ||||
Output | 0 | 0-10V/4-20mA |
|||
1 | RS485/Modbus |
Measuring range
Code |
UNIT & Range & Resolution for Display |
Accuracy(%FS) |
||||||||
Pa | Pa | KPa | In W.C | mm W.C | mbar | D5 |
D5P | D5G | D5T | |
1 | 0-60 |
60.00 |
0.060 |
0.250 |
6.000 |
0.600 |
3% | |||
2 |
0-125 |
125.0 |
0.125 |
0.500 |
12.50 |
1.250 |
2% | 2% | ||
3 | 0-250 | 250.0 | 0.250 | 1.000 | 25.00 | 2.500 | 1% |
1% | 1% | 1% |
4 |
0-500 |
500.0 |
0.500 |
2.000 |
50.00 |
5.000 |
1% | 1% | ||
5 | 0-1000 | 1000 | 1.000 | 4.000 | 100.0 | 10.00 | 1% |
1% | 1% | 1% |
6 |
0-2500 |
2500 |
2.50 |
10.00 |
250.0 |
25.00 |
1% | 1% | ||
7 | 0-5000 | 5000 | 5.000 | 20.00 | 500.0 | 50.00 | 1% |
1% | 1% | 1% |
8 | 0-10000 | 10000 | 10.00 | 40.00 | 1000 | 100.0 | 1% |
1% | 1% | 1% |
9 |
0-20000 |
20000 |
20.00 |
80.00 |
2000 |
200.0 |
1% | 1% |
Note: 1. 5 engineering units can be set by the key and related LCD will be on
2. For D5 and D5P,only ranges 3,5,7,8 are available
3. For zero center models, add "Z " at the end of the model.
For example, D5T3**Z, means -125-0-125pa. Only ranges 1~6 have this select ion.
Sample Order |
Order |
OEM Order |
Three work days | 2 weeks | 3 weeks |
Port
Shenzhen, Hong Kong